TURKCE

MAIN PAGE
ABOUT US
CONTACT
REFERENCES
DOWNLOAD
 
PRODUCTS
  10-40KVA 3000d/d    
  10-27KVA 1500d/d   
  30-75KVA 1500d/d
  100-200KVA 1500d/d  
  225-500KVA 1500d/d 
  600-1500KVA 1500d/d
 
GSA ALTERNATOR:
MECHANICAL SPECS
ELECTRICAL SPECS
PARALLEL RUNNING
ALTERNATOR SELECTION

42 TYPE GSA  ALTERNATORS

GENERAL INFORMATION ABOUT 42 TYPE

PRIME POWER RANGE (STANDBY)  100 - 220 KVA (110 - 220 KVA)
SPEED  /  NUMBER OF POLES 1500rpm  /  4 POLES
EXCITATION  /  INSULATION TYPE  SELF REGULATING, BRUSHLESS  / CLASS F
CONFORM STANDARDS VDE 0530; IEC 34-1; TS 3205-3206-3209
AMBIENT TEMPERATURE / ALTITUDE 40°C  /  from sea level to 1000m
PROTECTION  / CONSTRUCTION TYPE  IP 23  /  B3/ B14(Db.B.) - MD35(Sing.B.)

NOTE: All the information given in this page is about 231/400V 3-Phase alternators. If you need information about single-phase alternators or alternators with different voltage and frequence, please inform us

42 TYPE ALTERNATOR RATING TABLE

TYPE

Cos phi=0.8

 Speed RPM
Efficiency %
Drive Power(HP)
GD2-Kpm2
Weight (Kg)
SINGLE BEARING DOUBLE BEARING
PRIME KVA
STANDBY KVA
GSA 422 S/4 GSA 422 S/T4
100
110
1500
89 122 4.200 470
GSA 423 M/4 GSA 423 M/T4 125 138 1500 90 151 5.100 550
GSA424 M/4 GSA 424 M/T4 150 165
1500
90.5 181 5.880 580
GSA 425 L/4 GSA 424 L/T4 175 193
1500
91 210 5.700 640
GSA 426 L/4 GSA 426 L/C4 200 220 1500 91.5 238 5.800 692

 

42 SINGLE BEARING 42 DOUBLE BEARING
PART LIST PART LIST
DIMENSIONS DIMENSIONS

 

MOUNTING DETAILS OF 42 TYPE GSA ALTERNATOR WITH SINGLE BEARING

The dimensions of diesel engine's flywheels and its cover use in gensets should comform SAE J620d  and SAE J617c standards. In GSA alternators, the disc mounted to the engine's  flywheel and the adaptor of alternator mounted to the engine's flywheel cover are design according to these standards. The SAE standards of engines that will used in genset should be informed to us while ordering.

If the SAE number of diesel engine's flywheel and its cover are not known, please find the SAE numbers of your engine's flywheel and its cover by comparing the dimensions given in SAE J620d  and SAE J617c standards.

The adaptor and disc combinations of  42 type GSA alternators are given in the table below :

 

SAE ADAPTOR / DISC COMBINATIONS FOR 42 TYPE SINGLE BEARING GSA ALTERNATORS

ADAPTÖR

DİSK KAPLİN

3

11-1/2  

2

11-1/2

1

11-1/2  /  14

 

MOUNTING DETAILS OF 42 TYPE GSA ALTERNATOR WITH DOUBLE BEARING

In the gensets with double bearing alternators, the power is transmited to the alternator's rotor  with the coupling mounted to the end of alternator's shaft. The coupling should be elastic to minimise combustion of the diesel engine's effect on the alternator shaft. Gensan produces GK type couplings for mounting GSA alternators to diesel engines. GK 220 coupling is used in 100 and 125 KVA, GK 220 coupling is used in 150, 175 and 200 KVA alternators.

At the end of the alternator shaft, there is a screw hole according to DIN 332 standard for mounting or dismounting purposes of the pulley or the coupling. Mounting of the pulley or the coupling can be done by placing a mounting apparatus to the screw hole. For easier mounting, the coupling or the pulley should be machined to H7 tolerance and heated to 120-150ºC. Avoid any kind of heavy hammering to prevent the ball bearings from damaging.

If the Pulley-Belt System is used for transmission in GSA Alternators which are greater than 50 KVA, special ball bearings must be used. In certain cases please inform us while ordering.

GENSAN ELECTRICAL MACHINES CO.