Essential alternator power ratings for selecting appropriate alternator are given in the "PRODUCTS" links. The given power ratings are for 1000 meters altitude, 40°C ambient temperature and Cos phi=0,80. If the altitude is above 1000 meters, the ambient temperature is over 40°C and the Cos phi is less than 0,80 the alternator power can be calculated by finding the power improving coefficients given in Table2 and 3. If the necessary is provided concerning your load and environmental conditions, we may select the appropriate alternator type.

EXAMPLE: 

Power required: 50 KVA

Load and environmental conditions: Altitude 2000 m, temperature 50°C, Power factor of load: Cos phi=0,70

TABLE 2      Power reduction with heigh temp.

P/Pn Ambient temperature
Elevation
40°C
45°C
50°C
55°C
H=0-1000 m
1.00
0.96
0.92
0.86
H=1000-2000 m
0,96
0,92
0,86
0,79
H=2000-3000 m
0,92
0,86
0,79
0,72
H=3000-4000 m
0,86
0,79
0,72
0,64

Improving coefficient due to the altitude and temperature is 0,86(Table 2)

TABLO 3    Power reduction with cos phi

Cos phi
1- 0.8
0.7
0.6
0.5
0.4
0
P/Pn
1.00
0.95
0.88
0.84
0.80
0.72

 and improving coefficent due to the power factor is 0,95 (Table 3)

Alternator power which will be selected (Ns) :

Ns=Power Required / (0,86*0,95)=50 / (0,86*0,95)=61,3 KVA

Appropriate power value 63 kVA available is selected.

  